ADSS

ADSS Aramid DJ

Aramid double jacket design for aerial installation on transmission towers, high-voltage power lines and railway catenary; highly resistant to electromagnetic effect

1

Central strength member (FRP rod)

2

Optical fiber

3

Gel-filled loose tube

4

Water-blocking gel

5

Inner jacket

6

Aramid yarns

7

Jacket

All-dieletric design

Wide range of operating temperatures. Installation temperature down to -30°C

The most reliable among ADSS cables. Double tensile strength

Aerial installation on distribution and transmission lines up to 35 kV and above

For construction of communication lines between towns and cities with distances between towers reaching 500 meters

Max rated design tension up to 100 kN

Maximum rated design tension 4 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 12.8 14.8 18.3
Cable weight, kg/km 122.1 157.4 241.2
Minimum bending radius, mm 192 222 275
Maximum rated design tension 6 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 12.8 14.8 18.3
Cable weight, kg/km 122.9 157.7 241.2
Minimum bending radius, mm 192 222 275
Maximum rated design tension 7 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 12.9 14.8 18.3
Cable weight, kg/km 124.7 159.1 241.2
Minimum bending radius, mm 194 222 275
Maximum rated design tension 8 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 12.9 14.9 18.3
Cable weight, kg/km 126.3 160.6 241.9
Minimum bending radius, mm 194 224 275
Maximum rated design tension 10 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 13.0 15.0 18.4
Cable weight, kg/km 129.4 163.7 148.9
Minimum bending radius, mm 195 225 276
Maximum rated design tension 12 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 13.3 15.1 18.5
Cable weight, kg/km 135.4 169.4 250.4
Minimum bending radius, mm 200 227 278
Maximum rated design tension 15 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 13.8 15.6 18.8
Cable weight, kg/km 142.4 176.9 257.4
Minimum bending radius, mm 207 234 282
Maximum rated design tension 20 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 14.2 16.0 18.4
Cable weight, kg/km 152.4 186.9 250.2
Minimum bending radius, mm 213 240 276
Maximum rated design tension 25 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 14.7 16.4 19.5
Cable weight, kg/km 162.3 197.0 277.3
Minimum bending radius, mm 221 246 293
Maximum rated design tension 30 kN
Crush — 0.22 kN/cm
Fiber count, up to 72 (6х12) 96 (8х12) 144 (12х12)
Cable diameter, mm 15.1 16.7 19.9
Cable weight, kg/km 172.6 205.0 287.0
Minimum bending radius, mm 227 251 299
Start shopping
Operating temperature* -50°С...+70 °С
Installation temperature -30°С...+70°С
Transportation and storage temperature -50°С...+70 °С
Minimum bending radius 15x cable diameter
Design life 25 years

*-60°C…+70°C *upon request