OPGW C


Application: installation on medium and high-voltage power lines
1

Optical fiber

2

Stainless steel tube filled with water-blocking gel

3

Stranded wires (Aluminum-clad steel wires and /or aluminum alloy wires)

4

Stranded wires (Aluminum-clad steel wires and /or aluminum alloy wires)

Up to 96 fibers

Aluminum-clad steel wires are corrosion resistant

Aluminum alloy wires shield the high-voltage conductors from lightning strikes

Maximum rated design tension (MRDT), kN 15...125
Crush, kN/cm 1
Rated breaking strength (RBS) (without SSLTs), kN 25...210
Fiber count, up to 96
Cable diameter, mm 8...18
Cable weight, kg/km 200...1230
Elasticity modulus (final), kN/mm² 70...160
Short circuit capacity (initial temp 25°С), kA²•s 5...300
Short circuit current for 1s, kA 2...20
Start shopping
Operating temperature -50°C ... +85°C
* -60°C ... +85°C upon request
Installation temperature -30°C ... +50°C
Transportation and storage temperature -50°C ... +85°C
Minimum bending radius 20 x cable diameter
Design life 50 years