OPGW S


Application: installation on medium and high-voltage power lines
1

Central strength member (aluminum-clad Steel wires or aluminum alloy wires)

2

Optical fiber

3

Stainless steel tube filled with water-blocking gel

4

Stranded wires (Aluminum-clad steel wires and /or aluminum alloy wires)

5

Stranded wires (Aluminum-clad steel wires and /or aluminum alloy wires)

Up to 432 fibers

Aluminum-clad steel wires are corrosion resistant

Aluminum alloy wires shield the high-voltage conductors from lightning strikes

Maximum rated design tension (MRDT), kN 28...165
Crush, kN/cm 1
Rated breaking strength (RBS) (without SSLTs), kN 47...275
Fiber count, up to 432
Cable diameter, mm 11...25
Cable weight, kg/km 330...1530
Elasticity modulus (final), kN/mm² 70...160
Short circuit capacity (initial temp 25°С), kA²•s 5...550
Short circuit current for 1s, kA 4...30
Start shopping
Operating temperature -50°C ... +85°C
* -60°C ... +85°C upon request
Installation temperature -30°C ... +50°C
Transportation and storage temperature -50°C ... +85°C
Minimum bending radius 20 x cable diameter
Design life 50 years